Accommodation relating to health care provision
Requirement for Smoke alarms
During any period beginning on or after 1st October 2015 while the premises are occupied under a tenancy (or licence) the landlord must ensure that a smoke alarm is equipped on each storey of the premises on which there is a room used wholly or partly as living accommodation. A living room will include a lounge dining room and kitchen as well as a bathroom or toilet. It also includes a hall or landing. This means that a smoke alarm must be provided in working order on each storey. The RLA takes the view that mezzanines are caught by this legislation where they contain a room used wholly or partly as living accommodation. As regards individual flats located on one floor then there will have to be at least one alarm within the flat itself or alternatively are provided outside the flat on the same floor of the building, i.e. a communal alarm.
Likewise, for flats comprising more than one storey there will need to be a smoke alarm on each floor.
It is the location of an alarm which sounds which is crucial; not the positioning of detectors.
The Regulations do not stipulate what kind of alarm is required. Ideally it should be a hard wired alarm system. It can, however, be a single standalone alarm. Landlords are recommended by the RLA to fit ten year long life tamper proof alarms, otherwise there is a problem of batteries being taken out and not being replaced.
As a final note, heat detectors are not considered sufficient. It will have to be a smoke detector.
Carbon monoxide alarms
Additionally, landlords must ensure that there is a carbon monoxide alarm fitted in any room that is used partly or wholly as living accommodation which also contains any appliance which burns, or is capable of burning, solid fuel. This would include log and coal burning stoves and open fires, even if they are not normally in use, but does not include gas and oil boilers. If an open fireplace is purely decorative and not useable then it is not covered by the regulations.
Gas is not a solid and so there is no requirement to fit one near a gas boiler. It is still advisable as best practice however.
Checks
The landlord is specifically required to carry out a check to ensure that smoke alarms or carbon monoxide alarms installed to comply with the Regulations are in proper working order on the day a tenancy begins where it is a new tenancy. A new tenancy is a tenancy granted on or after 1st October 2015.
For these purposes a new tenancy does not include a tenancy which was granted where the original agreement was entered into before 1st October 2015; nor does it include a periodic statutory tenancy which arises when a fixed term shorthold tenancy ends. It does not apply to a tenancy which starts at the end of an earlier tenancy where the landlord and tenant are the same as under the earlier tenancy and the premises are the same (or substantially the same) as those under the earlier tenancy. Therefore this express requirement to check does not apply to the renewal of a tenancy for the same premises by the same landlord to the same tenant. This should not be confused with the requirement to install detectors and alarms which applies to tenancies in existence before October 1st 2015.
In our view, landlords should not be under a false sense of security because of this provision. Our reading of the regulation is that there is an ongoing obligation to ensure that any smoke alarm or carbon monoxide alarm installed to meet these requirements is in working order. Alarms should therefore be checked periodically to see that they are working properly. There is no reason why this responsibility should not be placed on the tenant and the government guidance does suggest the tenant check monthly. However, the landlord will then have to make sure that the tenant does actually carry out the checks. If challenged, a landlord could have to show that a proper system has been put in place to check alarms regularly.
Placement of Alarms
The regulations do not tell landlords where to place the alarms, instead the guidance suggests the landlord follow the manufacturer's instructions which will typically be at head height between 1-3 meters away from the solid fuel burning source for carbon monoxide alarms and in a circulation point for smoke detectors.
HMOs and Selectively licensed properties
As from 1st October 2015 new licence conditions will be included requiring the provision of smoke alarms and fire detectors. In the case of HMO licences they already contain provisions for alarms in any case. The regulations themselves are not applicable in this kind of accommodation.
Enforcement
The local authority is responsible for enforcement.
A local authority must serve a remedial notice within 21 days where they have reason to believe that the landlord is in breach of any of these duties relating to smoke alarms or carbon monoxide alarms. A remedial notice must specify the action to be taken within 28 days of the date of the service of the notice. It allows the landlord 28 days to make representations against the notice.
The landlord must then take the required action within the period allowed. There is an excuse for a landlord for non-compliance with the notice if the landlord can show that he has taken reasonable steps to comply with the duty, but the landlord is not required to take legal proceedings. This could cover a situation where the tenant refuses access to allow the work to be done.
If the landlord fails to take action then the local authority must, if it has the necessary consent to do so, arrange for the work required to be undertaken within 28 days of consent being obtained if consent of the occupier of the premises is required. Therefore if a local authority is also refused access by the tenant it cannot take the necessary steps itself.
Penalties
If the landlord is in breach the local authority may require the landlord to pay a penalty charge up to a maximum of £5,000. It has discretion whether or not to impose this charge. If it intends to impose a charge it must serve a penalty charge notice within six weeks from when it is first satisfied that a breach has occurred. A right to make representations against the penalty notice is given and the local authority may reduce the charge for prompt payment.
Appeals
If the local authority upholds a penalty charge notice there is a right to appeal for the landlord to the First Tier Tribunal. The Grounds of Appeal are:-